Skip directly to content

CP Wire

Click on the links below to explore our range of CP Wire products.

Downloads: 

1. High Molecular Weight Polyethylene (HMW-PE) Cathodic Protection Cables: 600 Volts, Single Conductor, Stranded Copper

600 Volts, Single Conductor, Stranded Copper

Application

A direct earth burial DC feeder cable for use in cathodic protection systems, for storage tanks, 

pipelines, wells, vessels and metallic structures either buried or water submerged. 

Standards

  1. Conductor - Stranded copper conductor conforms to ASTM B8.
  2. Insulation - Insulation is high molecular weight polyethylene conforming to ASTM D1248, Type 1, Class A, Category 5, Grades E4 & E5.
Size
No. of 
Strands
Circular
Mils
AWG
Diameter
Inches
Insulation
Thickness
Inches
Nominal
Diameter
Inches
Weight
Lbs per
1000 ft
DC Ohms 
per Mft
at 20ºC
#1474,110.0726.110.29338
2.57
#1276,530.0915.110.31148
1.62
#10710,380.116.110.34062
1.02
#8716,510.146.110.37087
.640
#6726,240.184.110.408122
.403
#4741,740.232.110.456175
.254
#2766,360.283.110.510260
.159
#11983,690.322.125.580330
.129
#1/019105,600.362.125.620401
.102
#2/019133,100.406.125.660492
.081
#4/019211,600.512.125.770750.05

 

2.Cathodic Protection Cables, Primary Halar Insulation, HMW (High Molecular Weight) Polyethylene Jacket

Application

A direct earth burial DC lead cable for use in deep anode groundbed installations, designed to withstand corrosive gases. 

Standards

  1. Conductor - Stranded bare copper conductor conforms to ASTM B8.
  2. Insulation -A homogeneous wall of natural ECTFE fluoropolymer (Halar) shall be extruded over the conductor.
  3. Jacket - Insulation is high molecular weight polyethylene conforming to ASTM D1248, Type 1, Class A, Category 5, Grades E4 and E5. 
Size
No. of 
Strands
Circular
Mils
AWG
Diameter
Inches
HALAR
Thickness
Inches
HMWPE
Thickness
Inches
Nominal
Diameter
Inches
Weight
Lbs per
1000 ft
DC Ohms 
per Mft
at 20ºC
#8716,510.146.020.065.31683
.640
#6726,240.184.020.065.354120
.403
#4741,740.232.020.065.402177
.254
#2766,360.283.020.065.462260
.159

 

3.Cathodic Protection Cables, Primary Kynar Insulation, HMW (High Molecular Weight) Polyethylene Jacket

Application

A direct earth burial, DC lead, cathodic protection cable for use in deep anode groundbed installations, designed to withstand corrosive gases.

Standards

  1. Conductor - Stranded bare copper conductor conforms to ASTM Specification B-8.
  2. Insulation - A homogeneous wall of natural PVDF fluoropolymer (Kynar) shall be extruded over the conductor.
  3. Jacket - Insulation is high molecular weight polyethylene conforming to ASTM-D-1248, Type 1, Class A, Category 5, Grades E4 and E5.
Size
No. of 
Strands
Circular
Mils
AWG
Diameter
Inches
Kynar
Thickness
Inches
HMWPE
Thickness
Inches
Nominal
Diameter
Inches
Weight
Lbs per
1000 ft
DC Ohms 
per Mft
at 20ºC
#8716,510.146.020.065.31683
.640
#6726,240.184.020.065.354120
.403
#4741,740.232.020.065.402177
.254
#2766,360.283.020.065.462260
.159